Fit-up Standards: Technical Reference Manual
Section A: General-purpose Office Space
A6. Sample Detail Drawings
A6.1 Workstations and Enclosed Offices
Open Workstations
Summary
Workstation accommodates average requirements for worksurface, shelving, storage and filing. Filing cabinets may be centralized as an alternative layout. The use of freestanding furniture components is encouraged for increased flexibility. Note: Furniture layouts are provided for example and may vary.
Height of filing cabinet may vary to suit workstation location (e.g., window locations - maximum two drawers high to allow transfer of natural light).
Standard Finishes
- Floor - base building standard carpet (rolled goods or carpet tile)
Standard Electrical Requirements - Workstations
- 3 standard electrical duplex receptacles (1 circuit per 2 workstations)
- 1 image/voice/data/outlet (Note: client to provide actual connectors and jacks, typically RJ45 with multiple jacks)
- Base building lighting
Examples of Workstation Layouts (cluster) 1.9 m² (20 ft²)
1.9 m² Workstation Layouts (cluster) is available on a separate page.
Example of Workstation Layouts (individual) 3.0 m² (32 ft²)
3.0 m² Workstation Layouts (individual) is available on a separate page.
Example of Workstation Layouts (cluster) 3.0 m² (32 ft²)
3.0 m² Workstation Layouts (cluster) is available on a separate page.
Examples of Workstation Layouts (individual) 4.5 m² (48 ft²)
4.5 m² Workstation Layouts (individual) is available on a separate page.
Examples of Typical Workstation Layouts (cluster) 4.5 m²
4.5 m² Workstation Layouts (cluster) is available on a separate page.
Examples of Workstation Layouts (individual) 5.9 m² (64 ft²)
5.9 m² Workstation Layouts (individual) is available on a separate page.
Examples of Workstation Layouts (cluster) 5.9 m² (64 ft²)
5.9 m² Workstation Layouts (cluster) is available on a separate page.
Examples of Workstation Layouts (individual) Maximum 7.4 m² (80 ft²)
7.4 m² Workstation Layouts (individual) is available on a separate page.
Examples of Workstation Layouts (cluster) 7.4 m² (80 ft²)
7.4 m² Workstation Layouts (cluster) is available on a separate page.
Enclosed Offices
Summary
Office accommodates average requirements for worksurface, shelving, storage and filing. Note: Furniture layouts are provided for example and may vary.
Finishes
- Floor - base building standard carpet (rolled goods or carpet tile)
- Walls - paint or unfinished (Note: partitions may be traditional construction or reusable system partitions, see A3.2 Fit-up Components and Funding Accountabilities)
Standard Electrical Requirements - Enclosed Offices
- 3 standard electrical duplex receptacles (2 circuits)
- 2 image/voice/data outlets (Note: client to provide actual connectors and jacks, typically RJ45 with multiple jacks)
- Base building lighting (may be relocated) with 1 separate switch/light control
Standard Mechanical Requirements
Interior zone:
- Individual thermostat control c/w dedicated terminal unit (VAV box, fan coil unit)
- Supply and return air diffuser(s)/grille(s)
Transfer return air fan c/w on/off switch for full height partitions
Perimeter zone (where required):
- Individual thermostat control for terminal units and perimeter system (convector(s), fan coil unit(s))
- Transfer return air fan c/w on/off switch for full height partitions
- Supply and return air diffuser(s)/grille(s)
- Noise abatement as required
Examples of Enclosed Office Layouts 10 m² (100 ft²)
Note: Minimum allowance for any position. See A3.3 Office and Support Space Allocations for further details.
10 m² Enclosed Office Layouts is available on a separate page.
Note: Example 3 provides for fully accessible office.
Examples of Enclosed Office Layouts 14 m² (150 ft²)
Note: Maximum allowance for EX-1 positions with 10 or more funded reports, senior departmental representatives at regional offices or remote locations, lawyers and ICMS employees. See A3.3 Office and Support Space Allocations for further details.
14 m² Enclosed Office Layouts is available on a separate page.
Examples of Enclosed Office Layouts 18.5 m² (200 ft²)
Note: Maximum allowance for EX-2 and EX-1 positions and equivalents no more than 3 levels below the DM (e.g., directors). See A3.3 Office and Support Space Allocations for further details.
18.5 m² Enclosed Office Layouts is available on a separate page.
Examples of Enclosed Office Layouts 23 m² (247.5 ft²)
Note: Maximum allowance for EX-3 positions and equivalents (e.g., directors general). See A3.3 Office and Support Space Allocations for further details.
23 m² Enclosed Office Layouts is available on a separate page.
Examples of Enclosed Office Layouts 28 m² (301 ft²)
Note: Maximum allowance for EX-5 and EX-4 positions and equivalents (e.g., ADMs, and members of boards, commissions and councils).
28 m² Enclosed Office Layouts is available on a separate page.